Kooltronic Maintenance
Kooltronic Water-Cooled Air Conditioners require no maintenance. Air-Cooled
Air Conditioners are designed to require only the routine cleaning of
air filters to assure unimpeded air flow through the condenser heat exchanger.
It is not possible to recommend specific filter cleaning intervals since
the level and the nature of airborne particulate matter differs widely
with each installation. It is generally sufficient to remove and wash
the reusable aluminum mesh air filters when the outer surfaces of these
filters appear covered with a thin layer of dust or lint. Filter recoating
adhesive is recommended. Appropriate disposable filters are available
from Kooltronic. If filter service is neglected or delayed, the air conditioner
will not perform at its design capacity. The first indication of excessively
clogged air filters is usually a gradual increase of temperature within
the equipment cabinet. If operation is continued under these conditions,
the compressor will be shut off by the thermal overload device. The compressor
will restart when its external temperature drops below the protector threshold
setting and the compressor will continue to cycle on and off. Continued
operation under these conditions will cause damage, shorten compressor
life and void the warranty.
Filter Removal and Service
Kooltronic Air Conditioners feature an easily removable inlet filter
to facilitate necessary cleaning.
CAUTION
- Loosen the screw on the bottom of the filter holder.
- Push the filter holder forward and move it down.
- Remove the filter from the filter holder.
- After removal, the filters should be flushed under warm running water
with the clean side up, driving contaminants out the dirty side of the
filter. If the accumulated dirt is oily, washing in a detergent bath
is recommended, followed by a warm water rinse as above.
- The filters may be sprayed with Kooltronic A-16 Filter Recoating Adhesive
to trap fine airborne contaminants, or they may simply be dried and
reinstalled as strainer type filters. Recoating is recommended for best
results.
- Reinstall the filter: Insert the filter inside the filter holder,
push the filter holder forward, move it up into place and replace the
screw on the bottom of the filter holder. Do not operate the Air Conditioner
for extended periods of time with the filter removed. The condenser
coil may become clogged with dust or lint from the air entering the
face. A clogged condenser coil is not readily detected and will give
the same reaction as a clogged filter. A clean filter is the best protection.
|